WATERLESS WG2A Smart Logic Controller

WATERLESS-WG2A-Smart-Logic-Controller-product

Impormasyon ng Produkto

Mga pagtutukoy

  • Modelo: Smart Logic Controller
  • Mga Pag-andar: Mga Pag-andar at Pagkakasunud-sunod ng PLC
  • Tagagawa: Total Green Mfg.
  • Kontrol: kontrolado ng PLC
  • Stage: 2-stage at mga multi-function na unit
  • Pagkakatugma: Gumagana sa iba't ibang mga heat/cool na thermostat

Disclaimer
Ang wastong pag-install at pagseserbisyo ng Total Green Mfg. Heat Pump ay mahalaga sa maaasahang pagganap nito. Lahat ng Total Green Mfg. system ay dapat na mai-install at maserbisyuhan ng isang kwalipikadong HVAC contractor. Ang pagpapalaki, pagpili at pag-install ng kagamitan ay ang tanging responsibilidad ng nag-i-install na kontratista.
Ang mga pag-install ng kagamitan sa isang kasalukuyang disenyo ng copper earth loop na hindi tumutugma sa kasalukuyang Total Green Mfg. earth loop na disenyo ay hindi pinahihintulutan, magpapawalang-bisa sa lahat ng warranty sa kagamitan, at ang tanging responsibilidad ng nag-i-install na kontratista. Ang pag-install ay dapat gawin alinsunod sa mga tagubiling itinakda sa manwal na ito. Ang pagkabigong magbigay ng pag-install ng isang kwalipikadong kontratista ng HVAC sa paraang naaayon sa manwal na ito ay magpapawalang-bisa at magpapawalang-bisa sa limitadong saklaw ng warranty para sa system.
Ang Total Green Mfg. ay hindi mananagot para sa anumang depekto, hindi kasiya-siyang pagganap, pinsala o pagkawala, direkta man o kinahinatnan, kaugnay sa disenyo, paggawa, konstruksiyon, aplikasyon o pag-install ng anumang mga bahaging tinukoy sa larangan.

Lahat ng Total Green Mfg. 2 stagAng mga e at multi-function na unit ay magkakaroon ng magkahiwalay na terminal strip na may label na "thermostat/zone board" at "air handler/furnace" para sa mababang voltage at ang PLC ay “controlled.
Para sa wastong paggana ng kagamitan, ang termostat o zone board ay dapat na nakatali sa strip na "thermostat/zone board terminal". Ang air handler o furnace ay dapat na nakatali sa terminal strip ng "air handler/furnace". Magkakaroon din ng karagdagang mga terminal strip para sa iba't ibang mga function batay sa uri ng modelo na maaari mong gamitin. Ang impormasyong ibinigay dito ay upang madagdagan ang manual ng pag-install na partikular sa iyong unit.

MAHALAGA: For WG2A, WG1AH, WG2AH and WG2AD unit’s, if using a cased coil over a furnace, do NOT program your thermostat for dual fuel mode or, use the furnace settings. Leave the thermostat set to electric aux. heat, otherwise, you may interfere with proper PLC function. Follow the dual fuel function option for the unit model you are installing. This information is detailed in your unit installation manual. You will also want to check the aux. heat cycle rate (CPH) setting in the thermostat and set this to 1 or, the lowest available value depending on your thermostat brand and model.

Smart Logic Controller

WG2A Forced Air Only– List of functions

  1. The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to
    “X”. During this 60 second time period, the compressor will only operate in 1st stage nagbibigay lang ng pagkakataon sa system na makabawi bago magtakda ng hard lock out. Ito ay upang maiwasan ang mga istorbo na tawag, lalo na sa simula ng panahon ng paglamig kapag ang Earth Loops ay nasa pinakamalamig na panahon. Nakatakda ang "X" sa anumang kondisyon ng hard lockout. Ang pagpihit sa mababang voltage sa compressor unit off then back on nire-reset ang lockout hangga't hindi nakabukas ang discharge temperature switch. Ang discharge temperature switch ay may manual reset button. Ang isang bukas na discharge temperature switch ay palaging mangangailangan ng manu-manong pag-reset kasama ng mababang voltage ikot ng kuryente. Ang mga switch ng pressure ay awtomatiko.
  2. A “Y1” call starts 1st stage heating o cooling na magpapatuloy sa loob ng 20 minuto at pagkatapos ay oras sa 2nd stage dapat lumipas ang oras na iyon nang walang tinatawag na "Y2" ang termostat. Kung ang unit ay nasa heating mode, isang beses 2nd stagMagsisimula, ang isang 20 minutong timer ay magdadala sa init ng AUX kapag lumipas ang oras na iyon nang hindi nasiyahan ang tawag sa pag-init. Kapag ang lahat ng stages ay tinawag na, mananatili silang tatawag hanggang sa ganap na nasiyahan ang thermostat.
  3. If more than 3 consecutive “Y1” calls take place without the thermostat calling for 2nd stage sa loob ng 20 minuto o, bago ang 20 minuto 2nd stagnaubusan ang timer, sa ikaapat na tawag na "Y1", magsisimula ang isang maintenance cycle na hahawak at i-lock ang system sa ika-2 segundotage para sa 5 minuto upang matiyak na bumalik ang langis sa compressor. Kung ang system ay air zoned, ang isang Zone Override terminal na "D" ay magpapasigla sa 24 volts. Gaya ng inilarawan sa iyong manwal sa pag-install ng unit, ang 24-volt signal na ito ay maaaring gamitin kasama ng isang field supplied na isolation relay upang tawagan ang buksan ang pinakamalaking zone at hawakan ang dampbukas para hindi makita ng blower ang mataas na static pressure sa loob ng 5 minutong iyon. Ang ikot ng pagpapanatili ay nagla-lock ng anumang iba pang tawag hanggang sa makumpleto. Pagkatapos ng maintenance cycle, o kung ang isang "Y2" na tawag ay ginawa bago mangyari ang maintenance cycle, ang counter ay magre-reset pabalik sa zero. Ginagawa nitong friendly ang aming system zone dahil pinapayagan nito ang totoong 2 stagay pag-init at paglamig.
  4. There is an installed jumper on the field wiring terminal block marked “A” and “S”. With the jumper installed, the unit will function with an aux heat strip as normal. If the jumper is removed, the PLC goes into dual fuel mode stopping the compressor when there is a call for aux heat. Once the aux heat call completes, a 5-minute cool down timer prevents the compressor from restarting on a “Y” call until the time elapses. This allows time for the furnace to cool so hot air doesn’t cause high discharge pressure or a lockout when the compressor restarts.
  5. When the thermostat is set to cooling mode, the “O” signal energizes the reversing valve and locks out the aux heat output.
  6. In an effort the reduce energy consumption, the PLC turns power off to the crank case heater when the compressor runs.
  7. This PLC program also allows the use of almost any heat/cool thermostat. Even if a single stage heat/cool lang ang thermostat ang ginagamit, ang PLC program ay magkokontrol sa lahat ng function stagsa 2nd stage at AUX Heat kung kinakailangan.

WGxAH Single at Dalawang Stage Forced Air na may Hydronic Heating Function

In addition to the function and features as described for WG2A units, The PLC program for the WGxAH units allows for switching priority call from forced air to hydronic heating as well as a feature
called “Split Zone” that are installer optioned by choosing jumper settings as described below.

  • A jumper is used on the field wiring terminal strip between the “R” and “AW” terminals to prioritize air heating over hydronic heating. When this jumper is removed, hydronic heating becomes the priority call.
  • Split Zone is a feature which allows you the ability to heat one zone or floor with hydronic heat and another zone or floor with forced air. Split Zone is active by removing the priority call jumper across “R” and “AW” moving it across the “R” and “SZ” of the field wiring terminal block.
  • While in “Split Zone” mode, the compressor unit will provided forced air heating to the air zone. When the buffer storage tank calls for heat, the compressor unit will shift to heat water. Should a call for the air zone take place while the compressor unit is heating water, the call goes directly to the aux heat source to maintain the air zone. Once the tank temperature is satisfied, the system diverts back to normal air heating with the compressor unit.
  • When a hydronic heat call from the buffer tank takes place, the compressor turns off if it is running. 1 minute after that, the circulator pump starts to establish good water flow, the 3 way valve energizes and the SV1 valve de-energizes. 1 minute after that the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
  • The Hydronic heating function is disabled anytime the “O’ terminal is energized placing the unit in cooling mode.

WG2AD Forced Air na may Domestic Water Heating Function

Bilang karagdagan sa pag-andar at mga tampok tulad ng inilarawan para sa mga yunit ng WG2A tulad ng inilarawan sa unang seksyon ng dokumentong ito, ang programa ng PLC para sa mga yunit ng WG2AD ay nagbibigay-daan para sa paglipat ng priyoridad na tawag mula sa sapilitang hangin patungo sa pagpainit ng tubig sa tahanan.

  • A jumper is used on the field wiring terminal strip between the “R” and “AW” terminals to prioritize air heating/cooling over domestic water heating. When this jumper is removed, domestic water heating becomes the priority call.
  • When a water heating call from the water tank takes place, the compressor turns off if it is running. 1 minute after that, the circulator pump starts to establish good water flow, the 3 way valve energizes and the SV1 valve de-energizes. 1 minute after that the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
  • An added functional PLC feature exclusive to the WG2AD model which allows water heating up 120 degrees, is the unit’s ability to maintain compressor stability by throttling the compressor load as needed to control discharge pressure.

WG1H 100% Hydronic Heated and Chilled Water Only– List of functions

  1. The PLC checks that the LOW/HIGH pressure, HX Low and Discharge temperature switches are made. An open safety switch input has a 60 second delay before setting a lockout and fault signal to “X”. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltage sa compressor unit off then back on nire-reset ang lockout hangga't hindi nakabukas ang discharge temperature switch. Ang discharge temperature switch ay may manual reset button. Ang isang bukas na discharge temperature switch ay palaging mangangailangan ng manu-manong pag-reset kasama ng mababang voltage ikot ng kuryente. Ang pressure at HX Low temperature switch ay awtomatiko.
  2. An “N” call starts the circulator pump for 30 seconds prior to the compressor to allow for full flow through the HX (heat exchanger) prior to starting the compressor. Once the call is complete, the pump will run an addition 30 seconds after the compressor stops to purge the HX of any residual heat. This occurs regardless of either a heated or chilled water call.

If you have any questions regarding any of these functions, please contact Total Green Mfg. at 419-678-2032 para sa teknikal na suporta.

Mga Madalas Itanong

  • T: Paano ko uunahin ang pag-init ng hangin kaysa sa hydronic na pagpainit sa mga yunit ng WGxAH?
    A: Remove the jumper between R and AW terminals on the field wiring terminal strip.
  • T: Paano gumagana ang tampok na Split Zone sa mga unit ng WGxAH?
    A: Move the jumper from R and AW terminals to R and SZ on the field wiring terminal block to activate Split Zone.