WATERLESS R-454B Smart Logic Controller

Disclaimer
- Ang wastong pag-install at pagseserbisyo ng Total Green Mfg. Heat Pump ay mahalaga sa maaasahang pagganap nito. Lahat ng Total Green Mfg. system ay dapat na mai-install at maserbisyuhan ng isang kwalipikadong HVAC contractor. Ang pagpapalaki, pagpili at pag-install ng kagamitan ay ang tanging responsibilidad ng nag-i-install na kontratista.
- Ang mga pag-install ng kagamitan sa isang kasalukuyang disenyo ng copper earth loop na hindi tumutugma sa kasalukuyang Total Green Mfg. earth loop na disenyo ay hindi pinahihintulutan, magpapawalang-bisa sa lahat ng warranty sa kagamitan, at ang tanging responsibilidad ng nag-i-install na kontratista. Ang pag-install ay dapat gawin alinsunod sa mga tagubiling itinakda sa manwal na ito. Ang pagkabigong magbigay ng pag-install ng isang kwalipikadong kontratista ng HVAC sa paraang naaayon sa manwal na ito ay magpapawalang-bisa at magpapawalang-bisa sa limitadong saklaw ng warranty para sa system.
- Ang Total Green Mfg. ay hindi mananagot para sa anumang depekto, hindi kasiya-siyang pagganap, pinsala o pagkawala, direkta man o kinahinatnan, kaugnay sa disenyo, paggawa, konstruksiyon, aplikasyon o pag-install ng anumang mga bahaging tinukoy sa larangan.
- All Total Green Mfg. forced air units will have separate terminal strips labeled “thermostat/zone board” and “air handler/furnace” for low voltage and are PLC “controlled.
- For proper equipment function, the thermostat or zone board must be tied to the “thermostat/zone board terminal” strip. The air handler or furnace must be tied to the “air handler/furnace” terminal strip. There will also be additional terminal strips for various functions based on the model type you may be working with. The information provided here is to supplement the installation manual specific to your unit.
- IMPORTANT: For WGxA, WG2AH and WG2AD unit’s, if using a cased coil over a furnace, do NOT program your thermostat for dual fuel mode or, use the furnace settings. Leave the thermostat set to electric aux. heat, otherwise, you may interfere with proper PLC function. Follow the dual fuel function option for the unit model you are installing. This information is detailed in your unit installation manual. You will also want to check the aux. heat cycle rate (CPH) setting in the thermostat and set this to 1 or, the lowest available value depending on your thermostat brand and model.
WG1A Forced Air Only– Listahan ng mga function
- The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to “X”. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltage sa compressor unit off then back on nire-reset ang lockout hangga't hindi nakabukas ang discharge temperature switch. Ang discharge temperature switch ay may manual reset button. Ang isang bukas na discharge temperature switch ay palaging mangangailangan ng manu-manong pag-reset kasama ng mababang voltage ikot ng kuryente. Ang mga switch ng pressure ay awtomatiko.
- A “Y” call starts heating or cooling. A 20-minute timer will bring on AUX heat should that time elapse without having satisfied the heating call. Once aux. heat is called, aux. heat will stay called until the thermostat fully satisfies.
- Mayroong naka-install na jumper sa field wiring terminal block na may markang "A" at "S". Kapag naka-install ang jumper, gagana ang unit na may aux heat strip gaya ng normal. Kung ang jumper ay tinanggal, ang PLC ay napupunta sa dual fuel mode na humihinto sa compressor kapag may tawag para sa aux heat. Kapag nakumpleto na ang aux heat call, pinipigilan ng 5 minutong cool down timer ang compressor na mag-restart sa isang "Y" na tawag hanggang sa lumipas ang oras. Nagbibigay-daan ito ng oras para lumamig ang furnace para hindi magdulot ng mataas na discharge pressure o lockout ang mainit na hangin kapag nag-restart ang compressor.
- Kapag ang thermostat ay nakatakda sa cooling mode, ang "O" na signal ay nagpapasigla sa reversing valve at nagla-lock out ang aux heat output.
- Sa pagsisikap na mabawasan ang pagkonsumo ng enerhiya, pinapatay ng PLC ang power off sa crank case heater kapag tumatakbo ang compressor.
- This PLC program also allows the use of almost any heat/cool thermostat. Total Green Mfg. Strongly recommends using Honeywell 8000 series thermostats.
- If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
WG2A Forced Air Only– Listahan ng mga function
- The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to“X”. During this 60 second time period, the compressor will only operate in 1st stage pagbibigay ng pagkakataon sa system na makabawi bago magtakda ng hard lock out. Ito ay upang maiwasan ang mga istorbo na tawag, lalo na sa simula ng panahon ng paglamig kapag ang Earth Loops ay nasa pinakamalamig na panahon. Nakatakda ang "X" sa anumang kondisyon ng hard lockout. Ang pagpihit sa mababang voltage sa compressor unit off then back on nire-reset ang lockout hangga't hindi nakabukas ang discharge temperature switch. Ang discharge temperature switch ay may manual reset button. Ang isang bukas na discharge temperature switch ay palaging mangangailangan ng manu-manong pag-reset kasama ng mababang voltage ikot ng kuryente. Ang mga switch ng pressure ay awtomatiko.
- Ang isang "Y1" na tawag ay magsisimula sa 1st stage heating o cooling na magpapatuloy sa loob ng 20 minuto at pagkatapos ay oras sa 2nd stage dapat lumipas ang oras na iyon nang walang tinatawag na "Y2" ang termostat. Kung ang unit ay nasa heating mode, isang beses 2nd stage starts, a 20-minute timer will bring on AUX heat should that time elapse without having satisfied the heating call. Once all stages ay tinawag na, mananatili silang tatawag hanggang sa ganap na nasiyahan ang thermostat.
- Kung higit sa 3 magkakasunod na "Y1" na tawag ang magaganap nang walang termostat na tumatawag para sa 2nd stage sa loob ng 20 minuto o, bago ang 20 minuto 2nd stagnaubusan ang timer, sa ikaapat na tawag na "Y1", magsisimula ang isang maintenance cycle na hahawak at i-lock ang system sa ika-2 segundotage for 5 minutes to assure oil return to the compressor. If the system is air zoned, a Zone Override terminal “D” will energize to 24 volts. As described in your unit installation manual, this 24-volt signal can be used along with a field supplied isolation relay to call open the largest zone and hold that damper open so the blower doesn’t see high static pressure during those 5 minutes. The maintenance cycle locks any other call out until completion. After the maintenance cycle, or if a “Y2” call is made before the maintenance cycle occurs, the
- counter resets back to zero. This makes our system zone friendly as it allows for true 2 stagay pag-init at paglamig.
There is an installed jumper on the field wiring terminal block marked “A” and “S”. With the jumper installed, the unit will function with an aux heat strip as normal. If the jumper is removed, the PLC goes into dual fuel mode stopping the compressor when there is a
call for aux heat. Once the aux heat call completes, a 5-minute cool down timer prevents the compressor from restarting on a “Y” call until the time elapses. This allows time for the furnace to cool so hot air doesn’t cause high discharge pressure or a lockout when the compressor restarts. - Kapag ang thermostat ay nakatakda sa cooling mode, ang "O" na signal ay nagpapasigla sa reversing valve at nagla-lock out ang aux heat output.
- Sa pagsisikap na mabawasan ang pagkonsumo ng enerhiya, pinapatay ng PLC ang power off sa crank case heater kapag tumatakbo ang compressor.
- This PLC program also allows the use of almost any heat/cool thermostat. Total Green Mfg. Strongly recommends using Honeywell 8000 series thermostats.
- If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
WG2AH Forced Air na may Hydronic Heating Function
In addition to the function and features as described for WG2A units, The PLC program for the WG2AH units allows for switching priority call from forced air to hydronic heating as well as a feature called “Split Zone” that are installer optioned by choosing jumper settings as described below.
- Ang isang jumper ay ginagamit sa field wiring terminal strip sa pagitan ng "R" at "AW" na mga terminal upang unahin ang air heating kaysa hydronic heating. Kapag naalis ang jumper na ito, ang hydronic heating ang magiging priyoridad na tawag.
- Ang Split Zone ay isang feature na nagbibigay-daan sa iyo na magpainit ng isang zone o sahig na may hydronic heat at isa pang zone o floor na may forced air. Ang Split Zone ay aktibo sa pamamagitan ng pag-alis ng priority call jumper sa "R" at "AW" na inilipat ito sa "R" at "SZ" ng field wiring terminal block.
- Habang nasa mode na "Split Zone", ang compressor unit ay magbibigay ng forced air heating sa air zone. Kapag ang buffer storage tank ay humihingi ng init, ang compressor unit ay lilipat sa init ng tubig. Kung ang isang tawag para sa air zone ay maganap habang ang compressor unit ay nagpapainit ng tubig, ang tawag ay direktang pupunta sa aux heat source upang mapanatili ang air zone. Kapag ang temperatura ng tangke ay nasiyahan, ang sistema ay lumilipat pabalik sa normal na pag-init ng hangin gamit ang compressor unit.
- When a hydronic heat call from the buffer tank takes place, the compressor turns off if it is running. 1 minute after that, the 3 way valve energizes and the SV1 valve de-energizes. 30 seconds after that stage, ang mga bomba ng tubig ay nagsisimulang magtatag ng magandang daloy ng tubig. 30 segundo pagkatapos noon stage, magsisimula ang compressor. Kapag nasiyahan na ang thermostat ng tangke, hihinto ang compressor at patuloy na tatakbo ang pump sa loob ng 30 segundo bago patayin upang makakuha ng anumang natitirang init mula sa heat exchanger. 1 minuto pagkatapos huminto ang compressor, ang 3-way na balbula ay nag-de-energize. 1 minuto pagkatapos nito ay maaaring mag-restart ang compressor para sa isang air zone call. Binabawasan ng mga naka-time na cycle na ito ang pagkasira ng bahagi ng system sa pamamagitan ng hindi kinakailangang paglipat sa ilalim ng presyon o pagkarga.
- Ang Hydronic heating function ay hindi pinagana anumang oras na ang "O' terminal ay pinasigla na inilalagay ang unit sa cooling mode.
- If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
WG2AD Forced Air na may Domestic Water Heating Function
Bilang karagdagan sa pag-andar at mga tampok tulad ng inilarawan para sa mga yunit ng WG2A tulad ng inilarawan sa unang seksyon ng dokumentong ito, ang programa ng PLC para sa mga yunit ng WG2AD ay nagbibigay-daan para sa paglipat ng priyoridad na tawag mula sa sapilitang hangin patungo sa pagpainit ng tubig sa tahanan.
- Ang isang jumper ay ginagamit sa field wiring terminal strip sa pagitan ng "R" at "AW" na mga terminal upang bigyang-priyoridad ang pagpainit/pagpalamig ng hangin kaysa sa domestic water heating. Kapag ang jumper na ito ay tinanggal, ang domestic water heating ang magiging priyoridad na tawag.
- When a water heating call from the water tank takes place, the compressor turns off if it is running. 1 minute after that, the 3 way valve energizes and the SV1 valve de-energizes. 30 seconds after that stage, ang mga bomba ng tubig ay nagsisimulang magtatag ng magandang daloy ng tubig. 30 segundo pagkatapos noon stage, magsisimula ang compressor. Kapag nasiyahan na ang thermostat ng tangke, hihinto ang compressor at patuloy na tatakbo ang pump sa loob ng 30 segundo bago patayin upang makakuha ng anumang natitirang init mula sa heat exchanger. 1 minuto pagkatapos huminto ang compressor, ang 3-way na balbula ay nag-de-energize. 1 minuto pagkatapos nito ay maaaring mag-restart ang compressor para sa isang air zone call. Binabawasan ng mga naka-time na cycle na ito ang pagkasira ng bahagi ng system sa pamamagitan ng hindi kinakailangang paglipat sa ilalim ng presyon o pagkarga.
- Ang isang karagdagang functional na feature ng PLC na eksklusibo sa modelong WG2AD na nagbibigay-daan sa pag-init ng tubig hanggang 120 degrees, ay ang kakayahan ng unit na mapanatili ang katatagan ng compressor sa pamamagitan ng pag-throttling ng compressor load kung kinakailangan upang makontrol ang discharge pressure.
- If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
Smart Logic Controller
WG1H 100% Hydronic Heated and Chilled Water Only– Listahan ng mga function
- Sinusuri ng PLC na ang LOW/HIGH pressure, HX Low at Discharge temperature switch ay ginawa. Ang isang bukas na safety switch input ay may 60 segundong pagkaantala bago itakda ang lockout at fault signal sa "X". Ito ay upang maiwasan ang mga istorbo na tawag, lalo na sa simula ng panahon ng paglamig kapag ang Earth Loops ay nasa pinakamalamig na panahon. Nakatakda ang "X" sa anumang kondisyon ng hard lockout. Ang pagpihit sa mababang voltage sa compressor unit off then back on nire-reset ang lockout hangga't hindi nakabukas ang discharge temperature switch. Ang discharge temperature switch ay may manual reset button. Ang isang bukas na discharge temperature switch ay palaging mangangailangan ng manu-manong pag-reset kasama ng mababang voltage ikot ng kuryente. Ang pressure at HX Low temperature switch ay awtomatiko.
- Ang isang "N" na tawag ay magsisimula sa circulator pump sa loob ng 30 segundo bago ang compressor upang bigyang-daan ang buong daloy sa HX (heat exchanger) bago simulan ang compressor. Kapag nakumpleto na ang tawag, tatakbo ang pump ng karagdagan 30 segundo pagkatapos huminto ang compressor upang linisin ang HX ng anumang natitirang init. Nangyayari ito anuman ang pinainit o pinalamig na tawag sa tubig.
- If the compressor unit sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor. The “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
Kung mayroon kang anumang mga katanungan tungkol sa alinman sa mga function na ito, mangyaring makipag-ugnayan sa Total Green Mfg. sa 419-678-2032 para sa teknikal na suporta.
Mga Madalas Itanong
- T: Maaari ba akong gumamit ng anumang thermostat sa Smart Logic Controller?
A: Yes, the PLC program allows for the use of almost any heat/cool thermostat, but Total Green Mfg. recommends using Honeywell 8000 series thermostats for optimal performance.
Mga Dokumento / Mga Mapagkukunan
![]() |
WATERLESS R-454B Smart Logic Controller [pdf] Gabay sa Pag-install R-454B, WGxA, WG2AH, WG2AD, R-454B Smart Logic Controller, R-454B, Smart Logic Controller, Logic Controller, Controller |